Alternator | Stamford, Leroy somer ,Marathon,Engga |
Control Panel | Smartgen, Deepsea,ComAp |
Rated Power | 500 kva |
Rated RPM | 1500rpm or 1800rpm |
Frequency | 50Hz or 60Hz |
Rated Voltage | 120v/208v,220V/380V, 240V/415V |
Product Name | 400kw diesel genset |
Place of Origin | China |
Brand Name | Cummins |
Certification | ISO9001:2008, CE |
Model Number | GNRC |
View Detail Information
Explore similar products
Silent 375kva Power Plant 300kw Cummins Diesel Generator engine 6ZTAA13 - G3
Automatic power 115kva 135kva Cummins Diesel Generator With 12 Hours Oil tank
Cummins Diesel Generator , Three Phase Brushless AC Generator
60Hz 1000kva Silent Electric Cummins Diesel Generator with engine kta38 - g2 DSE
Product Specification
Alternator | Stamford, Leroy somer ,Marathon,Engga | Control Panel | Smartgen, Deepsea,ComAp |
Rated Power | 500 kva | Rated RPM | 1500rpm or 1800rpm |
Frequency | 50Hz or 60Hz | Rated Voltage | 120v/208v,220V/380V, 240V/415V |
Product Name | 400kw diesel genset | Place of Origin | China |
Brand Name | Cummins | Certification | ISO9001:2008, CE |
Model Number | GNRC | ||
High Light | cummins generator set ,cummins industrial generator |
500kva Cummins Diesel Generator Stamford Direct Injection Kta19-G4
1.Chongqing Cummins Diesel Engine:KTA19-G4
2.Stamford AC Brushless Alternator:HCI544C
3.Deepsea,Smartgen Control Panel
4.Electronic Governor
Water Cooled Cummins Diesel Generator 500 kva Stamford Brushless Alternator
Type |
GNRC500 |
Frequency(50/60HZ) |
400KW/500KVA |
Standard configuration |
|
Sales commitment |
The products that we provide are all new, each unit all get through the strict production testing.
12 months or 1000 hours(whichever occurs first) of Warranty Time for all our products. We take the full responsibility only in the fault that created by the quality, the wearing-parts, daily consumables and human error of operating & maintenance are not included in.
Criterion |
The main parameters of the generator set |
MAIN SPECIFICATIONS OF GENERATOR SETS |
|
Diesel Generator Set |
|
GENSET MODEL NOS. |
GNRC |
Manufacturer |
Genor |
Rated speed / frequency |
1500RPM/50Hz |
Continuous outputKW/KVA |
400/500 |
Standby outputKW/KVA |
440/550 |
Voltage, Phase and wire |
400V/230V, 3 Phase and 4 Wires |
Rated power factor |
0.8lagging |
Dimension(L*W*H) (mm) |
3670*1220*1900 |
Weight(kg) |
4800 |
Rating Definitions (Operation at Altitude ≤1000m, Ambient temperature ≤ 40) |
|
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. |
|
Diesel Engine |
Cummins |
DIESEL ENGINE MODEL |
KTA19-G4(Cummins) |
Engine Characters |
Water-cooled, 4 cylinders in line, 4-cycle, direct injection |
The engine outputKW |
448 |
Aspiration |
Turbocharged & Aftercooled |
Bore(mm)×Stroke (mm) |
159*159 |
Compression ration |
14.5:1 |
Fuel consumption(L/H) |
101(100% load) |
Displacement(Liters) |
19 |
Exhaust air flow(m3/min) |
588 |
Compress air flow(m3/min) |
34.7 |
Exhaust gas flow(m3/min) |
96.2 |
Exhaust highest temperature |
557 |
Lub-oil pan capacity(L) |
50 |
Cooling water capacity(L) |
91 |
Voltage for start(V) |
24 |
Instrument for adjusting speed |
Electronically |
Noise level(A) |
≤85dBA(open) |
ALTERNATOR |
|
ALTERNATOR MODEL |
HCI544C |
Excitation |
Brushless |
Insulation class |
H |
Protection class |
IP22 |
Efficiency |
94.10% |
Voltage adjust range |
±1% with 4% engine governing |
Steady state voltage regulation |
≤±1% |
Voltage Control |
AVR |
Control system:
1 a) Automatic alarm system: the unit has the acousto-optics alarm system and arrestor for any situation as the
start defeat, the water is over temperature, the oil pulls down, over speed, over load and over current
b) Operation display:
i) Unit voltage, tri-phase load current and frequency display
ii) Water temperature, oil pressure display
iii) Fuel level, fuel temperature display
iv) Audible and visual alarm lamps and buzzers
2 Starting system: DC alternator is used to start engine
3 Short circuit protection: MCCB air switch
Standard Accessory
Common steel base frame, Damper, Exhaust silencer, Flexible pipe, Battery and connecting wires,
Operation manual and document.
Optional Accessory
Engine coolant and oil heater, Alternator space heater, Cooling for heat exchanger, Battery charger
by main supply, Fuel-water separator, Daily fuel tank, ATS & paralleling system, and Moving Trailer.
Soundproof/Silent Box:
1. Excellent ventilation
2. Oil tank mounted on base frame for 12 Hours working
3. Highly Corrosion Resistant construction
4. 1m<80 dB / 7m<70dB
Company Details
Business Type:
Manufacturer
Year Established:
2000
Employee Number:
200~300
Ecer Certification:
Verified Supplier
Genor Power Equipment Co., Ltd is a Chinese factory producing engine driven welder ,diesel generator set, gas generator set, Marine generator ,silent generators, trailer generators, lighting tower generators, industrial ceiling fan and other industrial equipments. The welder is from 160... Genor Power Equipment Co., Ltd is a Chinese factory producing engine driven welder ,diesel generator set, gas generator set, Marine generator ,silent generators, trailer generators, lighting tower generators, industrial ceiling fan and other industrial equipments. The welder is from 160...
Get in touch with us
Leave a Message, we will call you back quickly!