China Self Regulating Electric Heat Tracing For Chemical Plant
China Self Regulating Electric Heat Tracing For Chemical Plant

  1. China Self Regulating Electric Heat Tracing For Chemical Plant
  2. China Self Regulating Electric Heat Tracing For Chemical Plant

Self Regulating Electric Heat Tracing For Chemical Plant

  1. MOQ: 1 meter
  2. Price: USD0.5-USD5 per meter
  3. Get Latest Price
Supply Ability 10 million meters per year
Delivery Time in one month
Packaging Details plywood crates
Dimensions 0.2"x0.3" (5mm x 8mm) 12 AWG
Dielectric Strength Over 2000 volts
Property As per project application
Usage Chemical Plant
Flame Resistance Good
Wattage 39Watt/meter
Max. Exposure Temp. (°F) Power Off 260
Voltages Up to 480
Brand Name MICH
Model Number EHTTSCP
Certification ISO9001
Place of Origin China

View Detail Information

Contact Now Ask for best deal
Get Latest Price Request a quote
  1. Product Details
  2. Company Details

Product Specification

Supply Ability 10 million meters per year Delivery Time in one month
Packaging Details plywood crates Dimensions 0.2"x0.3" (5mm x 8mm) 12 AWG
Dielectric Strength Over 2000 volts Property As per project application
Usage Chemical Plant Flame Resistance Good
Wattage 39Watt/meter Max. Exposure Temp. (°F) Power Off 260
Voltages Up to 480 Brand Name MICH
Model Number EHTTSCP Certification ISO9001
Place of Origin China
High Light 2000V Electric Heat TracingSelf Regulating Electric Heat Tracing2000V constant wattage heating cable

Electric Heat Tracing Technical Solution for Chemical Plant is a package solution for the industrial processes to manufacture chemical product either in large scaled production or fine chemical production.

 


Electric Heat Tracing Technical Solution for Chemical Plant guarantees the maintenance of the temperature in the pipes, tanks and process equipment. That maintenance prevents any problem derived from losing temperature in processes: obstructions and breakages, increased viscosity in fluids, condensation of water steam in gases and phase shifts...


The solution normally uses parallel type heating cables (Self-regulating and/or Constant Power) and temperature control adapted to each process. All commanded by direct temperature and power control panels.

 

Here are five applications typically:

 

1. High Temperature Heat Tracing: for the use of temperature higher than 500°C
2. Long-Line Heating: for the use of pipeline more than 300 meters.

3. Freeze Protection: The main purpose of a freeze-protection system is to prevent fluids such as process water, drain water and fire water lines from freezing in pipes.
4. Process Temperature Maintenance without Steam Exposure: With process temperature-maintenance applications, there is usually a need for viscosity control of certain fluids such as fuel oils, acids and fertilizers at higher temperatures beyond freeze-protection applications.
5. Process Temperature Maintenance with Steam Exposure: In some freeze-protection and process temperature-maintenance applications, the heat-tracing cable is exposed to higher temperatures than the maintenance temperature when steam is used to clean the pipes.

 

Table 2 Heating Cable Specification (600V Single Conductor)

 

Cable Code Diameter HDPE Diameter Standard resistance value at +20 Maximum Production Length Unit weight
mm mm Ω/m m kg/km
16C1.7 8.2 10 0.0017 350 366.54
16C2.2 7.6 9.4 0.0022 380 307.77
16C2.9 7.0 8.8 0.0029 400 264.45
16C4 5.9 7.7 0.004 600 190.88
16C7 5.3 7.1 0.007 600 154.08
16C11 4.9 6.7 0.011 600 132.25
16C13 4.6 6.4 0.013 600 (300)☆ 125.7
16C17 4.6 6.4 0.017 600 (300)☆ 117.16
16C21 4.6 6.4 0.021 600 (300)☆ 111.9
16C25 3.7 5.5 0.025 600 (480)☆ 68.83
16C33 3.7 5.5 0.033 600 (480)☆ 63.76
16C40 3.4 5.2 0.04 600 (560)☆ 58.87
16C63 3.2 5 0.063 600 51.47
16K80 6.8 8.6 0.08 370 (140)☆ 254.18
16K100 5.2 7 0.1 450 (240)☆ 162.11
16K140 4.9 6.7 0.14 600 (270)☆ 122.55
16K197 4.45 6.25 0.197 600 (330)☆ 111.32
16K220 4.5 6.3 0.22 600 (330)☆ 102.89
16K315 4.3 6.1 0.315 600 (350)☆ 91.44
16K345 4.2 6.0 0.345 600 (370)☆ 85.9
16K450 4.0 5.8 0.45 600 (400)☆ 80.73
16K630 4.0 5.8 0.63 600 (400)☆ 77.26
16K800 3.5 5.3 0.8 600 (530)☆ 61.48
16K1250 2.8 4.6 1.25 600 40.83
16K2000 2.8 4.6 2.0 600 38.96

 

 

Table 3 Heating Cable Specification (600V Double Conductors)

 

Cable Code Diameter Nominal resistance at +20 Maximum manufacturing length Unit weight
mm Ω/m m kg/km
26C3.4 12.9 0.0034 150 783.76
26C4.4 12.2 0.0044 160 701.56
26C5.8 11.3 0.0058 170 606.16
26C8.6 9.90 0.0086 180 451.43
26C11.4 9.30 0.0114 200 400.05
26C13.8 9.00 0.0138 210 375.20
26C17.2 8.60 0.0172 220 344.90
26C23 8.00 0.023 250 303.25
26C34.4 7.50 0.0344 280 269.20
26C49.2 7.10 0.0492 300 243.84
26K240 9.90 0.24 180 451.43
26K320 9.30 0.32 200 400.05
26K384 9.00 0.384 210 375.20
26K480 8.60 0.48 220 344.90
26K640 8.00 0.64 250 303.25
26K960 7.50 0.96 280 269.20

 

 

Table 4 Heating Cable Specification (300V Double Cores)

 

Cable Code Diameter Nominal resistance at +20 Maximum manufacturing length Unit weight
mm Ω/m m kg/km
23C3.4 12.0 0.0034 200 708.10
23C4.4 11.3 0.0044 220 629.07
23C5.8 10.4 0.0058 240 537.73
23C8.6 9.00 0.0086 260 392.56
23C11.4 8.40 0.0114 280 343.89
23C13.8 8.00 0.0138 300 314.57
23C17.2 7.60 0.0172 320 286.27
23C23 7.10 0.023 340 252.98
23C34.4 6.60 0.0344 360 221.19
23C49.2 6.20 0.0492 380 197.64
23K160 10.4 0.16 220 508.37
23K240 9.00 0.24 240 392.56
23K320 8.40 0.32 265 343.89
23K384 8.00 0.384 280 314.57
23K480 7.70 0.48 300 291.91
23K640 7.10 0.64 320 252.98
23K960 6.50 0.96 350 216.11

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals;

Mark of (300)☆ is a recommended production length by MICH

 

Selection Parameters:

 

 

Constant Wattage Heating Cable High Temperature Heating cable Polyamide/Fiberglass Heating Cable Harsh Environment Heating Cable General Purpose Heating Cable
Available Voltages 120, 208, 240, 277 & 480 VAC 120, 208, 240, 277 & 480 VAC 120, 208, 240, 277 & 480 VAC 120, 208, 240, 277 & 480 VAC

Available Wattages

 

4, 8 & 12 watts/ft (13, 26 & 39 watts/m) 4, 8 & 12 watts/ft (13, 26 & 39 watts/m) 4, 8 & 12 watts/ft (13, 26 & 39 watts/m) 3, 5, 8 & 12 watts/ft (10, 16, 26 & 39 watts/m)
Maximum Exposure Temperature

500°F (260°C)

 

500°F (260°C)

 

500°F (260°C)

 

400°F (204°C)

 

Nominal Dimensions

 

0.2"x0.3" (5mm x 8mm) 12 AWG

 

0.2"x0.3" (5mm x 8mm) 12 AWG

 

0.2"x0.3" (5mm x 8mm) 12 AWG

 

0.2"x0.3" (5mm x 8mm) 12 AWG
Resistance to Moisture Good Good

Excellent

 

Excellent

 

Resistance to Chemicals Good Good

Excellent

 

Excellent

 

Resistance to Flame Excellent Outstanding Excellent Outstanding
Dielectric Strength Over 2000 volts

Over 2000 volts

 

Over 2000 volts Over 2000 volts

Company Details

Bronze Gleitlager

,

Bronze Sleeve Bushings

 and 

Graphite Plugged Bushings

 from Quality China Factory
  • Business Type:

    Manufacturer

  • Year Established:

    2008

  • Employee Number:

    150~200

  • Ecer Certification:

    Active Member

Pasia Industries is a scientific and technological enterprise specializing in researching, developing, producing, installing and providing technical consultation and service for mineral insulated heating cables, heating elements and finished heaters as well as welded honeycomb products for filtering... Pasia Industries is a scientific and technological enterprise specializing in researching, developing, producing, installing and providing technical consultation and service for mineral insulated heating cables, heating elements and finished heaters as well as welded honeycomb products for filtering...

+ Read More

Get in touch with us

  • Reach Us
  • Pasia Industries Ltd
  • 1200 N Fuxing Rd Wutong Dist Tongxiang 314500 Zhejiang P. R China
  • https://www.miheatingcables.com/

Leave a Message, we will call you back quickly!

Email

Check your email

Phone Number

Check your phone number

Requirement Details

Your message must be between 20-3,000 characters!

Submit Requirement